YOKOGAWA ADM12T 32-Point Contact Input Module (Terminal Type, CENTUM CS/VP)

The Yokogawa ADM12T is a 32-point contact input module with terminal-type connections for the CENTUM CS, CENTUM CS 3000, and CENTUM VP distributed control systems (DCS). It is a digital input module designed to acquire binary status signals from field devices such as limit switches, pushbuttons, and relay contacts. The "T" suffix denotes the terminal-type interface, which uses M4 screw terminals for direct field wiring, as opposed to the connector-type variants (ADM12C) that require external terminal boards.

  • رقم الصنف :

    ADM12T
  • الطلب (الحد الأدنى للكمية) :

    1
  • قسط :

    EXW
  • منشأ المنتج :

    Japan
  • ميناء الشحن :

    Wuhan, Hubei, China
  • مهلة :

    3-5 days
  • وزن :

    1kg
  • Brief Introduction of Yokogawa

    Yokogawa's main businesses: industrial automation and test and measurement hardware and software.

    Yokogawa's products are used in a variety of industries that require process control systems. Depending on the size and requirements of the project, Yokogawa offers a variety of control systems: DCS, PLC, SCADA and ESD (Emergency Shutdown). Yokogawa has also partnered with Shell Global Solutions to provide advanced process control (APC) solutions for refineries, petrochemical plants, and chemical plants.

    Detailed Information

    ADM12T Contact input module (32-point terminal type), 32 channels

    Country of origin

    Japan

    Product condition

    New

    Warranty

    one year

    Payment Method

    T/T, Western Union

    Shipping Method

    DHL/FedEX/UPS/TNE/EMS

    Company Introduction

    SWAN ELECTRIC has been in the industrial control industry for many years, specializing in providing PLC, DCS, control system spare parts, drives, HIM, etc.

    Main Brands: Rockwell-AB ¦ ABB ¦ Triconex ¦ Siemens ¦ ICS Triplex¦ Yaskawa ¦ Pilz ¦ Schneider ¦ Mitsubishi ¦ Honeywell ¦ GE Fanuc ¦ Sick ¦ Bently ¦Beckhoff¦ Omron ¦ Delta ¦ P+F ¦ Foxboro ¦Pilz ¦ B&R ¦Bachmann¦ Cisco¦MOXA¦B&R¦IFM......

    The purpose of the SWAN ELECTRIC is to maintain the production cycle of the factory.


    FAQ

    Q1: What is the Yokogawa ADM12T used for?
    It is a 32-point contact input module for CENTUM CS/VP DCS systems, used to acquire binary status signals from field devices such as limit switches, pushbuttons, and relay contacts .

    Q2: How many channels does it have?
    32 input points .

    Q3: What is the difference between ADM11T and ADM12T?
    The ADM11T provides 16 points; the ADM12T provides 32 points. Both are terminal-type modules .

    Q4: What is the difference between ADM12T and ADM12C?
    The ADM12T is the terminal type with built-in M4 screw terminals for direct field wiring. The ADM12C is the connector type, which requires an external terminal board and cable. They are not interchangeable .

    Q5: Does it support voltage input as well as dry contact?
    Yes. It supports both contact input (OFF ≥100 kΩ, ON ≤200 Ω) and voltage input (OFF 4.5–25 V DC, ON ±1 V DC) .

    Q6: What is the signal isolation configuration?
    The official specification states each point is isolated, with a common minus side every 16 points . Note that some third-party listings incorrectly claim channel-to-channel isolation.

    Q7: What is the response time?
    The module supports pulse widths ≥40 ms and pulse periods ≤10 Hz .

    Q8: Is this a current or legacy product?
    The ADM12T is associated with CENTUM CS/VP systems and is primarily sourced as a spare part for existing installations. Confirm current availability with Yokogawa or an authorized distributor.

    Q9: Where can I get technical documentation?
    The official Yokogawa General Specification (TI 33K01A12-50E) documents the ADM12T as a "Contact Input Module (32 Points, Terminal Type)" . Consult Yokogawa or an authorized distributor for the exact order number.


    Recommending Models

     
     
    Model Description When to Choose
    ADM12T 32-point contact input module, terminal type When high-density (32-point) contact input with direct field wiring is required in CENTUM CS/VP
    ADM11T 16-point contact input module, terminal type When fewer input points (16) are sufficient
    ADM12C 32-point contact input module, connector type When pre-fabricated cabling with an external terminal board is preferred (not interchangeable with T-type)
    ADM51T Contact output module (terminal type) When digital output capability is required alongside inputs (confirm with Yokogawa)
ترك رسالة
إذا كنت مهتمًا بمنتجاتنا وترغب في معرفة المزيد من التفاصيل، فيرجى ترك رسالة هنا، وسنرد عليك في أقرب وقت ممكن.
ترك رسالة