FAQ
Q1: What is the Bachmann CS200 used for?
It is a CANopen slave head module used to build modular CANopen slave stations from Bachmann M1/M200 I/O modules. It enables distributed I/O architectures for automation systems .
Q2: What is the difference between CS200 and CS200/N?
The CS200 (00013178-00) is the standard version requiring an external 24 V power supply. The CS200/N (00013179-00) includes an integrated power supply (18–34 VDC, 17 W nominal) .
Q3: How many I/O modules can be connected?
Up to 15 I/O modules per station directly, expandable to 30 using bus extension modules (BES/BEM) or FASTBUS .
Q4: What CANopen features are supported?
CANopen to CiA DS 301 V3.0, device profiles DS 401 and DS 402, 128 TxPDO/128 RxPDO, variable PDO mapping, 4 SDO servers, and heartbeat/node guarding .
Q5: What is the maximum bus length?
Up to 5000 m, with signal repeaters required for long distances .
Q6: What are the serial interfaces?
COM1 is RS232; COM2 supports RS232/422/485 .
Q7: Is the CS200 suitable for marine applications?
Yes, it carries marine certifications including GL/DNV, LR, ABS, and BV .
Q8: Where can I get technical documentation?
Official Bachmann electronic documentation, or an authorized distributor, is the authoritative source for specifications and compatibility.
Recommending Models