SIEMENS 7MH4900-2AA01 Control Module

The Siemens 7MH4900-2AA01 is a SIWAREX FTA (Flexible Technology, Automatic Weighing Instrument) single-channel weighing module for SIMATIC S7-300 and ET 200M systems. It is designed for legal-for-trade (calibratable) automatic weighing applications, including high-speed dosing, filling, bagging, and totalizing.

  • رقم الصنف :

    7MH4900-2AA01
  • الطلب (الحد الأدنى للكمية) :

    1
  • قسط :

    EXW
  • منشأ المنتج :

    Germany
  • ميناء الشحن :

    Wuhan, Hubei, China
  • مهلة :

    3-5 days
  • وزن :

    0.360kg
  • Overview

    7MH4900-2AA01 Siemens Simatic PLC Module

    New in stock     

    Origin from Germany

    Payment Method: TT.Western Union

    Shipping Method: DHL\UPS\Fedex\EMS\Others 

    More Brands

    Why Choose Us

    FAQ

    1. How do I calibrate the SIWAREX FTA using SIWATOOL FTA?

    • Brief procedure:

    1. Connect the PC to the SIWAREX FTA module via the RS232 interface and launch the SIWATOOL FTA software. 

    2. Enable Service Mode (Service Mode = 1). 

    3. Configure the parameters in Data Record 3 (DR3), including weighing units, resolution range, and calibration weight. 

    4. Execute the "Set zero valid" (set to 3) and "Adjustment weight 1 valid" (set to 4) commands in sequence. 

    5. Disable Service Mode (Service Mode = 2) to complete the calibration.

    • For a detailed calibration workflow, please refer to the SIWAREX FTA calibration guide (PDF).

     

    2. Is it possible to upload a program file from an MMC (Micro Memory Card) and download it to a new module using SIWATOOL V4 or SIWATOOL FTA software?

    • Answer: No. It is not possible to directly extract configuration files from an MMC and download them to a replacement module using SIWATOOL software. When a module is replaced, parameters must be reconfigured and the unit must be recalibrated.

     

    3. What software is required to integrate a SIWAREX weighing module into SIMATIC PCS7?

    • Answer:

    • The corresponding version of the HSP (Hardware Support Package) must be installed. 

    • AS function blocks: SFT_AWI (FB461) for scale control, CMD_AWI (FB647) for commands, and MOD_SIWA (FB648) for diagnostics and maintenance. 

    • OS panels: These provide a standard view, a dosing view, and a service view.

     

    4. What are the primary interfaces and I/O configurations of the module?

    • I/O configuration: 7 digital inputs (DI), 1 control input (CI), 8 digital outputs (DQ), and 1 analog output (AQ). • Communication and weighing interfaces: 1x RS485, 1x RS232, and 1x load cell (LC) interface (supporting 1–4 mV/V).

     

    Hot Sale Recommendation

    6GK1503-3CB00    6ES7416-3XR05-0AB0
    6EP1334-2BA20    6ES7972-0BA12-0XA0
    6EP1333-2AA00 6ES7138-4FR00-0AA0 
    6EP4135-0GB00-0AY0 6ES7136-6BA00-0CA0 
    6ES7153-1AA03-0XB0    6ES7158-0AD01-0XA0
    6ES7321-1BL00-0AA0    6ES7193-4CC20-1AA0
    6ES7331-7NF00-0AB0    6ES7193-4CB20-0AA0
ترك رسالة