Recommended Models & Related Products
What's Included
Note: PROFIBUS cable, network devices, and programming tools are sold separately.
Why Buy From Us?
-
In Stock – Ready to ship immediately
-
Genuine Siemens Product – Factory original SIMATIC NET component
-
Warranty Included – Purchase with confidence
-
Technical Support – PROFIBUS network configuration assistance available
Frequently Asked Questions (FAQ)
Q1: What is the Siemens 6GK1500-0FC10?
It is a PROFIBUS FC RS 485 bus connector with a 180° axial cable outlet and FastConnect insulation displacement technology. It is used to connect PROFIBUS nodes to the bus cable in industrial automation networks .
Q2: What is the difference between the 0FC10 and the 0FC00?
The 0FC10 (this item) has a 180° axial cable outlet (straight back). The 0FC00 has a 90° right-angle outlet. The choice depends on the physical orientation of the PROFIBUS port on your device and the available space in the cabinet.
Q3: What is FastConnect?
FastConnect is Siemens' insulation displacement connection technology for PROFIBUS cables. It allows the cable to be connected without stripping the insulation or using screws—the wires are pressed into the connector's contacts, which pierce the insulation and make electrical contact .
Q4: Does this connector have a terminating resistor?
Yes. It has an integrated terminating resistor that is activated via a slide switch. When activated, the resistor terminates the bus and the isolating function disconnects the outgoing bus segment to prevent signal reflection .
Q5: When should I activate the terminating resistor?
Activate the terminating resistor only when the connector is at the first or last physical node of the PROFIBUS segment. In all other positions, the terminating resistor must be off .
Q6: What transfer rates does this connector support?
It supports PROFIBUS transfer rates from 9.6 kbit/s to 12 Mbit/s .
Q7: What type of cable does this connector use?
It uses 2-core PROFIBUS FC installation cable with FastConnect insulation displacement terminals. Standard PROFIBUS cables may also be compatible if the conductor dimensions match, but FC cable is recommended for the fastest installation .
Q8: Is this connector suitable for hazardous areas?
Yes. It carries ATEX, FM, CCC-Ex, and IECEx approvals for hazardous locations, in addition to UL/cULus and marine certifications .
Q9: What is the operating temperature range?
The connector operates from -40 to +70 °C .
Q10: What are the dimensions and weight?
Dimensions are 16 × 62 × 34.5 mm (W × H × D). Net weight is 40 g .
Q11: Does this connector have a PG connection socket?
No. This variant does not include a PG (programming device) connection socket . If a PG socket is required for temporary programming connections, a different variant should be selected.
Q12: What should I verify before ordering?
Always verify the exact part number (6GK1500-0FC10 for 180° outlet), confirm your device's PROFIBUS port orientation and available cabinet space, ensure your PROFIBUS cable is compatible with FastConnect technology, and check whether the ATEX/IECEx approvals are required for your installation environment.